ELS safety case

What protects the operator, in which machine state, against which failure — and, just as importantly, where nothing does.

This page exists because the guards were accreting one incident at a time with no stated policy, so safety calls stalled for weeks at a time. It is an enumeration with citations plus the decisions that enumeration forces. It is not a certification, and nothing here has been through fault injection.

Provenance

Enumerated by reading the source at bd10c92, then updated for the four commits of 2026-08-31 (7f2191d, eedc4da, a0068d2, 308b920). Every row cites a file and line. Where a fact could not be confirmed by reading code it is marked UNVERIFIED rather than asserted — see Open questions, which is the most important section on this page.


The decision this page had to make

The task that produced this document set a behavioural acceptance bar: decide the servo-mode divergence watchdog's escalation, or admit the page is theatre.

Decided 2026-08-31 — the watchdog escalates to a NOTICE, not to alarm.

rung what it does motion risk status
log-only writes a line to the journal none, and no benefit either — at the lathe there is a touchscreen and no terminal, so this reached nobody superseded
notice amber line on the top status bar via els_uic.notify none — touches no motion path ADOPTED
alarm on_enter_alarm → drops sync, then the feed, then set_enable(False) a false positive stops the feed with the tool in the groove and de-energizes the drive, freeing the leadscrew NOT TAKEN

The reasoning is asymmetric and that asymmetry is the whole argument. A false positive on the notice rung costs one amber line. A false positive on the alarm rung is itself a hazard event — the detector would cause the class of incident it exists to detect. The alarm rung stays closed.

Sync enable controls the servo drive

servoEnableTask drives a real enable pin (Ramps.c:1672-1673): servoMode != 0 takes ENA low and the drive is energized; servoMode == 0 takes it high, the drive is disabled, and the leadscrew is free to turn by hand. That is what "releasing the carriage hold" means, and it is why on_enter_alarm's ordering matters — it drops sync first, so escalating really would release the leadscrew mid-pass.

Note this is a different hold from elsStop.active, which gates sync-step accumulation; clearing that one is the "go" for a pass (Ramps.c:1247). Two holds, and a single phrase that used to be attached to the wrong one.

Landed in a0068d2. Watchdog at ui/reflex/dispatchers/servo.py:232.


Machine states

From ui/reflex/fsms/els_fsm.py:20-24 — five, mirrored into the UI FSM as in_cycle.cutting / in_cycle.retracting / alarm.

state meaning operator exposure
disabled no job armed; machine inert lowest
stopped armed and holding at the shoulder tool may be in the work
retracting powered move back toward start Z tool dragged along the thread if X is not clear
cutting feeding under spindle sync highest
alarm faulted, disarmed recovery only

Coverage matrix

Failure class × state. = a mechanism gates motion. = detected and reported, but nothing is gated. GAP = nothing found.

failure class disabled stopped retracting cutting alarm
Spindle-encoder loss GAP GAP GAP GAP GAP
Z-scale loss GAP GAP GAP ✓ at take-up only GAP
Modbus loss GAP GAP GAP GAP
Drive fault GAP GAP GAP GAP GAP
UI death n/a GAP GAP GAP GAP
Firmware re-asserts feed after UI said stop
Leadscrew turned while the drive is off GAP GAP GAP GAP

That table is mostly GAP, and that is the finding. It is not evidence the machine is dangerous — it is evidence that what protects the operator today is the take-up confirmation gate and the operator's own hands, and that the protection is concentrated almost entirely at one moment (the start of a pass) in one state (cutting).

Required behaviour, per failure class

Spindle-encoder loss. Should stop the feed. Today nothing detects it, in any state. A dead encoder during cutting presents as zero sync deltas, which is indistinguishable in the searched code from "the spindle stopped turning" — a condition toggle_engage deliberately treats as safe (ui_controller.py:1181-1214). Whether that ambiguity is hazardous depends on drivetrain behaviour not established here. Grep for encoder.*loss|encoderFault|servoFault across fw/Core and ui/reflex returns zero hits.

Z-scale loss. Should stop the feed. The take-up gate (Ramps.c:944-1067) and its confirm-window abort (:1086-1124) and 5 s timeout backstop (:1126-1137) do exactly this — but only at take-up, at the start of a pass. There is no continuous Z-liveness check through a cut.

Modbus loss. Should stop the feed. els_fsm.py:271-276 escalates an unacknowledged stop-write to alarm, and it is the only mechanism found that handles a Modbus-shaped failure. It is scoped to on_enter_cutting. A link drop while retracting — a powered move — is not covered. Note also that a protocol-version mismatch at connect (board.py:249-297) is deliberately non-fatal: it warns and permits engage.

Drive fault. Should stop the feed. No register, ISR check or UI path referencing a driver fault line was found. This may not be a software gap at all — the design writes step/dir directly from STM32 pins, so a fault line may not exist in the hardware. Confirm before treating this row as work.

UI death. Should stop the feed — a live cut with no supervisor is the worst cell in the table. Nothing in firmware times out a feed when the UI stops polling. Guard #25 above is UI-initiated (it fires on a failed write ack) and therefore cannot fire when the UI is the thing that died. The firmware's take-up gates run independently of UI liveness, but they only run at take-up.

Leadscrew turned while the drive is off. Should invalidate the thread reference. It does not — see the gap called out under Open questions. Dropping sync de-energizes the drive, the leadscrew becomes hand-turnable, and nothing clears referenceLatched short of an engage cycle. This one is a code gap rather than an unwritten feature, and it is the only row here where the machine can end up confidently wrong rather than merely unprotected.


What exists, by layer

19 mechanisms gate motion in release-shipping code — 9 firmware, 10 UI. The figure this page was commissioned to check was "~7", which appears to have been a guess: no commit or document anywhere arrives at 7.

Firmware, release builds (fw/Core/Src/Ramps.c)

# mechanism cite
1 Take-up Z/slip confirmation gate :944-1067
2 Take-up confirm-window abort — never overwrites a real verdict with OK :1086-1124
3 Take-up timeout backstop (5 s); recovery only via enable 1→0 :1126-1137
4 Jog-mode (servoMode==2) take-up refusal :1273-1307
5 Calibration request refusal (enabled / wrong mode / bad config) :644-676
6 Calibration abort on condition change mid-run :681-691
7 Enable falling-edge teardown — cancels pending take-up and all commanded motion so nothing survives the edge as banked debt :792-832
8 ELS_REQUIRE_QUIESCENCE AND-gate :907-1035
9 Hysteresis re-latch guard :1159-1178

Guard 8 is dormant in every build ever shipped

ELS_REQUIRE_QUIESCENCE defaults to 0 (Ramps.c:67-68) and the flag has never shipped on. Its protection — ANDing a "carriage genuinely stopped" test into the take-up gate — does not exist on any machine in the field. If a safety argument leans on it, that argument is fictional today.

Guard 7 is what makes disengage-while-armed physically safe. Two diagnostic probes (els_diag_disengage_latch.h, els_diag_mode_watch.h) provide a belt-and-braces net during bring-up and are compiled out of release builds entirely — they must never be counted as release protection.

UI, release builds

Ten refusals: disengage-while-armed (ui_controller.py:1181-1214), no-Z-axis and summed-Z engage refusals (:1231-1267), FSM double-tap guards, the calibration CRC/fabricated-read guard (els_cal.py:258-339), calibration protocol-version and config refusals, and the three thread-resync refusals (els_resync.py).

Changed 2026-08-31

The three thread-resync refusals now fire when the wizard opens, not at the Begin button (eedc4da). They previously refused only after the operator had followed the jog instructions — moving the carriage by hand, closing the half nut, and hauling it back against the flank. The conditions are unchanged; the timing was the defect.

Reported but not gating

The servo-mode divergence watchdog (now a notice, see above), the take-up outcome torn-snapshot guard (ui_controller.py:546-635), and two display integrity guards that fail in deliberately opposite directions: the phase offset holds its last value on a read failure (:677-694) because 0 would read as "no offset being cut", while the thread-ref-latched lamp hides (:740-786) rather than show a stale latch. Neither gates motion; both exist so the screen cannot lie.

A new UI-visibility guard landed the same day (308b920): the ADV button refuses to hide the advanced ELS bar while a stop job is engaged, because that bar is the only place armed-ness is visible anywhere in the UI.

Not a guard, despite appearances

stepPulseRuntCount (Ramps.c:769-779) is a pure counter. Grepped across fw/ and ui/: no consumer takes any refuse, alarm or latch action on it. It is read only for logging into a capture file. It lives in guard-adjacent ISR code and its register comments describe it in guard-like language, which is exactly why it is called out here.


Open questions

A latched thread reference survives sync being switched off

This is a gap in the code, not in the enumeration, and it follows directly from the note above.

Dropping sync de-energizes the drive, so the leadscrew can be turned by hand. There is no leadscrew feedback — the firmware knows only commanded steps — so anything that moves while the drive is off is invisible to it, and a thread reference latched before that point no longer describes the machine.

Firmware clears referenceLatched only on the elsStop.enable 0→1 edge (Ramps.c:781-783, and Ramps.h:191 says so). stop_sync() clears syncEnable on every scale and touches nothing else. So sync off and back on without an engage cycle carries the old reference across, and the UI keeps showing REF LATCHED.

That path is not hypothetical: it is what the 2026-08-30 bench run walked when Sync Enable was pressed mid-cut, toggled again, and the job resumed without disengaging.

Evan, 2026-08-31: "when sync is disabled the leadscrew can be rotated freely. That's why it's imperative that a latched phase ref must be cleared when sync is disabled." It currently is not.

Two more, both cheap to close and neither closed here:

  • Does a drive fault line exist in the hardware at all? If not, that matrix row is not a software gap and should be struck rather than carried.
  • Is spindle-encoder loss actually distinguishable from a stopped spindle at the drivetrain? If it is not, no software detector can be written, and the answer belongs in the encoder-integrity work (index channel plus per-rev checksum) rather than here.

How to use this page

When a safety call comes up, find the cell. If it is , the mechanism is named and cited — go read it rather than re-deriving it. If it is GAP, that is not a bug report; it is a statement that the protection was never written, and the decision in front of you is whether it should be.

Two standing rules this page asks you to keep:

  1. Never count a diagnostic-build mechanism as release protection. Two of them exist and both are compiled out.
  2. Never count guard 8. It is present in the source and absent from every machine.